Underfloor heating

Air-to-water heat pumps for underfloor heating: output, water temperature and flow.

Underfloor heating is well suited to heat pumps because it can operate with low water temperatures. Good performance still depends on a proper heat-loss calculation, sufficient flow and sensible zone control.

Key information

  • Typical water temperature: 30–35°C
  • Series to review: AQ-Vento R290 and AQ-Casa R32
  • Key comparison: Capacity and COP at A7/W35 and the design point

Size from the real heat load

Use the building heat loss at the local design outdoor temperature. Floor area can provide a rough check, but it cannot replace a room-by-room or building calculation.

  • Include fabric, ventilation and climate
  • Keep DHW duty separate from space heating
  • Check available output below zero

Hydraulics and control

The heat pump must retain minimum flow when zones close. A buffer, hydraulic separator or bypass should answer a specific water-volume or control need, not be added by habit.

  • Balance the floor circuits
  • Use weather compensation before high fixed setpoints
  • Provide enough active water volume to limit cycling

Checks before selection

ItemCheck
Design heat loadCompare it with capacity at the minimum outdoor temperature.
Water temperatureUse the temperature the floor actually requires.
ΔT and flowKeep both within the unit and circuit operating range.
ZonesConfirm what happens when several thermostats close.

Mistakes to avoid

  • Sizing from floor area alone.
  • Setting 45–50°C without a design need.
  • Ignoring minimum flow in heavily zoned systems.

Frequently asked questions

Is a buffer tank always required?

No. Use one when system volume, flow, defrost or zone control creates a clear need.

Which COP should I compare?

Compare values at the same air/water condition, starting with A7/W35 and then checking the winter design point.