Key information
- Starting point: Design heat load
- Unit check: Capacity at the required A/W condition
- Final check: Minimum modulation, hydraulics and power supply
Good sizing starts with heat loss at the design outdoor temperature and ends with a check of actual unit capacity at the required water temperature. Floor area and nominal output are not enough.
You need location, design outdoor temperature, heat loss, emitters, water temperature, DHW, power supply and sound constraints. An estimate can guide early work but cannot replace technical verification.
Use manufacturer tables at the proposed outdoor and water temperatures. Also check minimum modulation in mild weather and any planned electric backup.
| Step | Result |
|---|---|
| 1. Load | kW required at the design outdoor temperature. |
| 2. Water temperature | Flow temperature required by the emitters. |
| 3. Model | Available capacity at the same A/W condition. |
| 4. System | Flow, water volume, DHW, electrical and sound checks. |
It can help when adjusted for weather, generator efficiency and actual occupancy, but should be checked against design heat loss.
That depends on the energy strategy and design temperature; state the bivalent point and any backup explicitly.